Temporary Above Ground Fuel Tank Permit Information
Storage areas shall be kept free from weeds and extraneous combustible material. Open flames & smoking prohibited in storage area.
Tanks & containers shall be conspicuously marked with name of product and the words "FLAMMABLE-KEEP FIRE AND FLAME AWAY" and "KEEP 50 FEET FROM BUILDING".
Metal containers shall be in accordance with DOT requirements or approved design. Pumping devices or self-closing faucets used for dispensing shall not leak and be well-maintained. Containers shall not be interconnected.
Tanks shall not exceed 10,000 gallons and of single-compartment design.
Tanks shall be at least 50 feet from buildings and combustible storage.
Tanks shall be provided with top openings only or shall be elevated for gravity discharge.
Tanks shall be mounted on well-constructed metal legs with shoes or runners to stabilize the entire tank and can be moved as a unit or for stationary tanks, on a stable base of timbers or blocks approximately 6 inches in height which prevents the tank from contacting the ground.
Tanks with top openings shall be equipped with tightly and permanently attached, approved pumping device with approved hose and locking device.
Gravity-dispensing tanks shall be mounted and equipped with supports to elevate the tank designed to carry required loads and provide stability. Tanks shall be equipped with a valve located adjacent to the tank which will close automatically in the event of fire through a heat-activated releasing device. Gravity discharge outlet shall have approved hose with a locking self-closing valve at the discharge end.
Outdoor storage areas shall be provided with drainage control or diking as set forth in IFC 3404.2.10.